134
5 SEQUENCE INSTRUCTIONS
5.1 Contact Instructions
Pulse operation start, pulse series connection, pulse parallel
connection
LDP, LDF, ANDP, ANDF, ORP, ORF
Processing details
LDP, LDF
LDP is the rising edge pulse operation start instruction, and is ON only at the rising edge of the designated bit device (when
it goes from OFF to ON). If a word device has been designated, it is ON only when the designated bit changes from 0 to 1.
In cases where there is only an LDP instruction, it acts identically to instructions for the creation of a pulse that are executed
during ON (P).
LDF is the falling edge pulse operation start instruction, and is ON only at the falling edge of the designated bit device
(when it goes from ON to OFF). If a word device has been designated, it is ON only when the designated bit changes from
1 to 0.
(S): Devices used as contacts (bits)
Setting
data
Internal device R, ZR J\ U\G Zn Constant Others
DX
Bit Word Bit Word
(S) 
Basic
Process
High
performance
Redundant
Universal
LCPU
X1/D0.1
X1/D0.1
Bit device number / Word device bit designation ( )
X2/D0.2
X2/D0.2
X3/D0.3
X3/D0.3
S
LDP
LDF
ORP
ANDP
ANDF
ORF
X0
D0K0MOV
M0
X0
Ladder using an LDP instruction
X0
D0K0MOVP
X0
Ladder not using an LDP instruction
M0
PLS