6 BASIC INSTRUCTIONS
6.1 Comparison Operation Instructions
BIN 32-bit data band comparisons
DZCP(P)
Processing details
One of (D), (D)+1, and (D)+2 turns on depending on the results (small, within the band, large) after comparison data (S3),
(S3)+1 is compared with the lower limit values (S1), (S1)+1 and the upper limit values (S2), (S2)+1.
When the contact turns off, "(D) to (D)+2" hold the conditions immediately before the contact turns on and off.
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Precautions
Set values smaller than the upper limit values (S2), (S2)+1 as the lower limit values (S1), (S1)+1. If the lower limit values
(S1), (S1)+1 are larger than the upper limit values (S2), (S2)+1, the upper limit values (S2), (S2)+1 will be handled as the
same values as the lower limit values (S1), (S1)+1.
LCPU: The serial number (first five digits) is "16042" or later.
QnUDVCPU: The serial number (first five digits) is "16043" or later.
(S1): Start number of the devices where the lower limit value is stored (BIN 32 bits)
(S2): Start number of the devices where the upper limit value is stored (BIN 32 bits)
(S3): Head number of device where data for comparison or comparison data is stored (BIN 32-bit)
(D): Head number of devices where the comparison results are stored (Bit)
Setting
data
Internal device R, ZR J\ U\G Zn Constant
K, H
Others
Bit Word Bit Word
(S1)  
(S2)  
(S3)  
(D)  
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4101 The range of 3 points from the device specified in (D) exceeds the range of
the corresponding device.

Basic
High
performance
Process
Redundant
Universal
Ver.
LCPU
Ver.
S3S2S1
DZCPP
DZCP
DZCPP
DZCP
S3S2S1
D
D
Command
Command
DZCP
Contact
S1 S2 S3 D
D
D
D+2
+1
S1 S3
S1
[
[
[
[
[
]
]S2S3
S1
S1
+1
+1
]
]
+1
+1
]+1
>,
,
,
,
,[
[]+1
]+1
,
,>S2S3
Turns on when
Turns on when
Turns on when
S2
S2
S3
S3
S3
≤≤