8 INSTRUCTIONS FOR DATA LINK
8.2 Reading/Writing Routing Information
827
8
Registering routing information
S(P).RTWRITE
Processing details
Registers routing information of (S) or later in the area for the transfer destination network number specified by n in the
routing parameters.
The following shows the contents of data to be set at (S) or later.
[Specification range of relay station number]
If data for the transfer destination network number specified by n is set in the routing parameters, it is used to update the
data in the area starting from (S).
If data in both (S)+0 and (S)+1 are 0, data for the transfer destination network number specified by n are deleted from the
routing parameters.
LCPU: The serial number (first five digits) is "13012" or later.
n: Transfer destination network No. (1 to 239) (BIN 16 bits)
(S): Head number of the devices where the data to be written is stored (Device name)
Setting
data
Internal device R, ZR J\ U\G Zn Constant
K, H
Others
Bit Word Bit Word
n 
(S)  
CPU module Registration number
High Performance model QCPU
Process CPU
Redundant CPU
Universal model QCPU whose serial number (first five digits) is "14111" or earlier
High-speed Universal model QCPU whose serial number (first five digits) is "15042" or earlier
•LCPU
Up to 64 modules
The Universal model QCPU whose serial number (first five digits) is "14112" or later, (except the High-speed
Universal model QCPU)
High-speed Universal model QCPU whose serial number (first five digits) is "15043" or later
Up to 238 modules
Network type Specification range
MELSECNET/H 1 to 64
CC-Link IE Controller Network 1 to 120
CC-Link IE Field Network Master station: Fixed at 125.
Local station: 1 to 120
Process
High
performance
Redundant
Basic
LCPU
Ver.
Universal
Command
S.RTWRITE
Command
n
SP.RTWRITE
n
S.RTWRITE
SP.RTWRITE
S
S
Relay station number
+0
+1
+2
Dummy
Relay network number
(Individual data ranges)
See the table below.
S

Table of Contents

Related product manuals