5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
169
5
Pulse conversion of direct output
DELTA (P)
Processing details
Conducts pulse output of direct access output (DY) designated by (D).
If DELTA DY0 has been designated, the resulting operation will be identical to the ladder shown below, which uses the
SET/RST instructions.
The DELTA (P) instruction is used by commands for rising edge execution for an intelligent function module.
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
(D): Bit for which pulse conversion is to be conducted (bits)
Setting
data
Internal device R, ZR J\ U\G Zn Constant Others
DY
Bit Word Bit Word
(D)
[Operation]
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4101 The specified direct access output number exceeds the CPU module output
range.

Basic
Process
High
performance
Redundant
Universal
LCPU
Command
Command
DELTA
DELTAP
D
DELTA
D
DELTAP
X100
DY0DELTA
X100
DY0SET
DY0RST
[Ladder using the SET/RST instructions][Ladder using the DELTA instruction]
X100
ON
OFF
DY0
ON
OFF
ON
END processing
DELTA DY0 DELTA DY0