EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q/L - Batch Reset of Bit Devices

Mitsubishi Electric MELSEC-Q/L
1084 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
416
7 APPLICATION INSTRUCTIONS
7.4 Bit Processing Instructions
Batch reset of bit devices
BKRST(P)
Processing details
Resets bit device n-points from the bit device designated by (D).
If the designated device is OFF, the device status will not change.
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
(D): Head number of the devices to be reset (bits)
n: Number of the devices to be reset (BIN 16 bits)
Setting
data
Internal device R, ZR J\ U\G Zn Constant
K, H
Others
Bit Word Bit Word
(D) 
n 
Device Status
Annunciator (F) Turns device n-points from annunciator (F) number designated by (D) OFF.
Deletes annunciator number turned OFF from SD64 to SD79 and compresses remaining data forward.
Stores number of annunciators stored from SD64 to SD79 at SD63.
Timer (T)
Counter (C)
Sets the current value n-points from timer (T) or counter c designated by (C) to 0, and turns coil contact OFF.
Bit devices other than the
above
Turns OFF coil or contact n-points from the device designated by (D).
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4101 The points specified in n exceed those of the corresponding device specified
in (D).

Basic
Process
High
performance
Redundant
Universal
LCPU
Command
Command
BKRSTP
BKRST
n
n
D
D
BKRST
BKRSTP

Table of Contents