7 APPLICATION INSTRUCTIONS
7.6 Structure Creation Instructions
487
7
Refresh
COM
Refer to Page 489 Select refresh (COM) for the COM instruction of the following CPU modules.
Processing details
Use the COM instruction for the following purposes.
The processing of the COM instruction differs depending on the status (ON or OFF) of the special relay SM775.
*1 The following processing is performed in communication with external devices.
*2 The auto refresh includes the following processing:
At the point of the execution of the COM instruction, the CPU module temporarily stops the processing of the sequence
program, and performs the same operation as ordinary data processing as well as auto refresh of intelligent function
modules (including link refreshes) at the END processing. However, the low speed cyclic refresh of MELSECNET/10 or
MELSECNET/H is not performed.
The COM instruction can be used in a sequence program any number of times. Note, however, that the scan time of the
sequence program will increase by the time taken for communication with external devices and auto refresh (including link
refresh) of intelligent function modules.
Basic model QCPU of serial No. 04122 or later
High Performance model QCPU of serial No. 04012 or later
Process CPU of serial No. 07032 or later
Redundant CPU
Universal model QCPU
•LCPU
Setting
data
Internal device R, ZR J\ U\G Zn Constant Others
Bit Word Bit Word

To reduce the time required to send/receive data to/from the remote I/O stations.
To ensure data communication with a CPU module on another station when two CPU modules perform operations using different scan times.
SM775 is OFF: Performs both auto refresh and communication with external devices.
*1*2
SM775 is ON: Performs only communication with external devices.
*1
Monitor processing of other station
Read processing by the serial communications module of the buffer memory of another intelligent function module
Refresh of MELSECNET/10, MELSECNET/H
CC-Link refresh
Auto refresh of intelligent function modules
Redundant
Basic
Process
High
performance
Universal
LCPU
COM
COM
0
END
0
END
0
Execution of COM instruction Execution of COM instruction
General data processing and auto refresh
(including link refresh) of intelligent function module