ADRSET(P)
• Stores the indirect address of the device designated by (S) at (D) and (D)+1. The address stored at the device designated
by (D) is used when an indirect device address is performed by the sequence program.
• A bit device designation cannot be made at (S).
See Page 105 Indirect Specification for further information on indirect designations.
• There is no operation error in the ADRSET(P) instruction.
(S): Number of the device whose indirect address is read out (Device name)
(D): Head number of the device where the indirect address of the device designated by (S) will be stored (BIN 32 bits)
Setting
data
Internal device R, ZR J\ U\G Zn Constant Others
Bit Word Bit Word
(S)
(D)
Basic
Process
High
performance
Redundant
Universal
LCPU
Command
Command
ADRSET
ADRSETP
S D
S D
ADRSET
ADRSETP
MOV K1234 @D100
ADRSET W100 D100
D0
D1
D100
D101
1234
W100
Stores the address of W100 address to D100 and D101.
Reads the contents of D100.
Device area
Address of
W100
Writes 1234 to the address
specified by D100 and D101.