6 BASIC INSTRUCTIONS
6.4 Data Transfer Instructions
299
6
Floating-point data transfer (single precision)
EMOV(P)
*1 Applicable for the Universal model QCPU, LCPU.
Processing details
Transfers 32-bit floating decimal point type real number data being stored at the device designated by (S) to a device
designated by (D).
When an input value is set using a programming tool, a rounding error may occur. For precautions, refer to Page 89
Precautions.
Operation error
There is no operation error in the EMOV(P) instruction.
Basic model QCPU: The serial number (first five digits) is "04122" or later.
(S): Data to be transferred or number of the device to which the data to be transferred is stored (real number)
(D): The number of the device to which the transferred data will be stored (real number)
Setting
data
Internal device R, ZR J\ U\G Zn Constant
E
Others
Bit Word Bit Word
(S)  
*1

(D)  
*1

Basic
Process
High
performance
Redundant
Universal
LCPU
Ver.
Command
Command
EMOV
EMOVP
S D
S D
EMOV
EMOVP
4.23542 4.23542
+1
+1
32-bit floating-point
real number
32-bit floating-point
real number
S DS D
Transfer