170
5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
Program example
The DELTA(P) instruction is used for setting preset values of high-speed counter modules.
The following program presets CH1 of the QD62 mounted at slot 0 of the main base unit, when X20 goes ON.
[Ladder Mode]
[List Mode]
Stores the preset value (0) in the buffer
memory addresses (0 and 1) of the QD62.
Outputs the preset command.
0LD X20
1 DMOVP K0
6 DELTAP DY1
8END
Step Instruction Device