5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
153
5
Program example
The following program turns Y10 and Y14 ON 10 seconds after X0 has gone ON.
The following program uses the BCD data at X10 to X1F as the timer's set value.
The following program turns Y10 ON 250ms after X0 goes ON.
[Ladder Mode] [List Mode]
(1) The setting value of the low-speed timer indicates its default time limit (100ms).
[Ladder Mode]
[List Mode]
[Ladder Mode] [List Mode]
(1) The setting value of the high-speed timer indicates its default time limit (10ms).
(1)
Step
Instruction
Device
Converts the BCD data at X10 to X1F to BIN
and stores the converted value at D10.
When X2 is turned ON, T2 starts measurement
using the data stored in D10 as the set value.
Y15 goes ON at the count-up of T2.
Step
Instruction
Device
(1)
Step
Instruction
Device