180
5 SEQUENCE INSTRUCTIONS
5.6 Termination Instructions
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4200 The END instruction was executed before the execution of the NEXT
instruction and after the execution of the FOR instruction.

4211 The END instruction was executed before the execution of the RET
instruction and after the execution of the CALL, FCALL, ECALL, or EFCALL
instruction.

4221 The END instruction was executed before the execution of the IRET
instruction in an interrupt program.

4230 The END instruction was executed between the CHKCIR to CHKEND
instructions.

4231 The END instruction was executed between the IX to IXEND instructions. 