7 APPLICATION INSTRUCTIONS
7.3 Shift Instructions
SFTWL(P)
This instruction shifts the n1 words data in the devices starting from the device specified by (D) to the left by n2 words.
n1=9, n2=4
The n2 words in the devices starting from the lowest device are filled with 0s.
If the value specified by n1 or n2 is 0, the instruction will be not processed.
If the value of n2 is equal to or greater than the value of n1, the n1 words devices starting from the device specified by (D)
will be filled with 0s.
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4100 The value in n1 or n2 is negative. 
4101 The points specified in n1 exceed those of the device specified in (D). 
10 0 7FF 3A 1F 30 0 FF
Filled with 0H
+2
+1
D D
+3
D
+4
D
+5
D
n2
+6
D
+7
D
+8
D D
n1
+2
+1
D D
+3
D
+4
D
+5
D
+6
D
+7
D
+8
D D
1FF
HH H HH H HH
0
H
0
H
0
H
0
H
H
3A 1F 30 0 FF
HHHH H