7 APPLICATION INSTRUCTIONS
7.6 Structure Creation Instructions
The EFCALL (P) instruction is used in combination with the ECALL (P) instruction.
If the EFCALL(P) instruction is used in conjunction with the ECALL(P) instruction, non-execution processing of a subroutine
program is performed when the execution command is turned OFF, enabling forcible turning OFF of the OUT instruction
and the PLS instruction (including P instructions). In case the EFCALL(P) instruction is not used in conjunction with the
ECALL(P) instruction, non-execution processing of a subroutine program is not performed even if the execution command
is turned OFF. Therefore, output status of the individual coil instructions remains unchanged.
Only the file name of a program file stored in the drive 0 (program memory/internal RAM) can be designated for a file name.
It is not necessary to designate the extension (.QPG) with the file name. (Only .QPG files will be acted on.)
[File Name: ABC.QPG]
[File Name: ABC.QPG]
When EFCALL instruction is used
Forced OFF by FCALL instruction
When EFCALL instruction is not used