582
7 APPLICATION INSTRUCTIONS
7.11 Character String Processing Instructions
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
For MIDR instruction
For MIDW instruction
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4101 The value of (S2) exceeds the number of characters specified by (S1).
The amount of (S2) and (S2) +1 exceeds the number of characters of (S1).
The (S2)+1 number of characters from position (D) exceeds the (D) device
range.
The (S2)+0 value is 0.
The values of (S2)+1 are those other than the effective values (-1, 0, 1 or
over).
There is no NULL code "00H" within the range of the corresponding devices
starting from the device number specified by (S1).

Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4101 The value of (S2) exceeds the number of characters specified by (D).
The amount of (S2) and (S2) +1 exceeds the number of characters of (S1).
The (S2)+1 value exceeds the number of characters for (S1).
The (S2)+0 value is 0.
The values of (S2)+1 are those other than the effective values (-1, 0, 1 or
over).
There is no NULL code "00H" within the range of the corresponding devices
starting from the device number specified by (S1).
