7 APPLICATION INSTRUCTIONS
7.11 Character String Processing Instructions
593
7
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Program example
The following program converts the BCD type floating decimal point format data being stored in devices starting from D0 to
32-bit floating decimal point type real number data based on the decimal fraction digit being stored at D10, and stores the
result at D100 and D101 when X0 goes ON.
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4100 The data format in the device specified by (S1) is not 0 or 1.
A value other than 0 to 9 exists in the each digit of (S1)+1 and (S1)+2.
The data format in the device specified by (S1)+3 is not 0 or 1.
The exponent data in the device specified by (S1)+4 is not within the range
from 0 to 38.
The decimal fraction digit specified by (S2) is not within the range between 0
and 7.

4101 The range of the device specified by (S1) exceeds that of the corresponding
device.

[Ladder Mode] [List Mode]
[Operation]
Instruction
Device
Step
D0
D10
D1
D2
D3
D4
1
4567
H
0123H
1
3
3
1234567H (BCD 7 digits)
D101
D100
1. 2 3 4 5 6 7