EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q/L - Page 748

Mitsubishi Electric MELSEC-Q/L
1084 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
746
7 APPLICATION INSTRUCTIONS
7.18 PID Instruction
Determining the three PID constants (step response method) [Reference]
To obtain good control result of PID control, optimal values of individual constants (parameters) appropriate to the controlled
system need to be determined. Here, the step response method is explained as a method of determining the optimal values of
three PID constants (proportional gain (K
P
), integral time (T
I
), and derivative time (T
D
)).
Step response method
The step response method is a method of determining three PID constants from the operation characteristics (maximum ramp
(R), dead time (L)) that are determined from changes in input caused by giving stepwise output from 0 to 100%
*1
to the control
system.
*1 Stepwise output can also be obtained in 0 75% or 0 50%.
Operation characteristics
Operation characteristics and three constants
Precautions on auto tuning
Programming measures in case of no change in the input value (PV)
If the input value (PV) does not change normally due to a factor such as analog input disconnection, auto tuning does not end.
Detect and avoid such problem by using a sequence to monitor the input value and the elapsed time from the start of tuning.
Control mode Proportional gain (K
P
) [%] Integral time (T
I
) [100ms] Derivative time (T
D
) [10ms]
Proportional control (P
operation) only

PI control (PI operation) 33L
PID control (PID operation) 20L 50L
0%
100%
MV
MV
Time
Time [s]
Maximum ramp (R)
Dead time (L) 1
[s]
Rate of change
in input value
RL
1
× MV × 100
RL
0.9
× MV × 100
RL
1.2
× MV × 100

Table of Contents

Related product manuals