776
7 APPLICATION INSTRUCTIONS
7.19 Other Instructions
Others
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Program example
The following program stores the model name of a module having the start I/O number 0020H in the area starting from D0
when X0 is turned on.
The specified slot is empty or the target module is during online module change.
The specified value (n) is not the start I/O number.
The specified value (n) is within the allowable setting range, but cannot be set in the I/O assignment setting screen of the PLC parameter dialog box.
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
2110 The target module cannot be communicated due to a failure. 
4101 The range of the device specified by (D) exceeds that of the device that can
be used.

The value specified in n is not within the range from 0 to FFH or 3E0H to
3E3H.

The value specified in n is not within the range from 0 to FFH or 3E0H. 
[Ladder Mode] [List Mode]
D
-1
b15 to b8 b7 to b0
00
H
00H
00H
00H
00H
00H
00H 00H
00H 00H
00H 00H
00H 00H
00H 00H
00H
00H
Stores -1.
Stores 00
H.
Indicates that the model
name is not stored.
+0
D
+1
D
+2
D
+3
D
+4
D
+5
D
+6
D
+7
D
+8
D
+9
Nine words are used.
Instruction
Device
Step

Table of Contents

Related product manuals