APPENDICES
Appendix 1 Operation Processing Time
Basic instructions
The processing time when the instruction is not executed is calculated as follows:
Q00JCPU: 0.20 (No. of steps for each instruction + 1) s
Q00CPU: 0.16 (No. of steps for each instruction + 1) s
Q01CPU: 0.10 (No. of steps for each instruction + 1) s
FEND
END
Error check performed 660 600 520
No error check performed
Battery check
Fuse blown check
I/O module verification
660 600 520
NOP 0.20 0.16 0.10
NOPLF
PAGE
0.20 0.16 0.10
Instruction Condition (device) Processing time (s)
Q00JCPU Q00CPU Q01CPU
LD= In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
AND= When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
OR= When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
LD<> In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
AND<> When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
OR<> When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
LD> In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
AND> When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
OR> When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
LD<= In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
AND<= When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
OR<= When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
LD< In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
AND< When not executed 0.70 0.56 0.35
When
executed
In conductive status 0.80 0.64 0.40
In non-conductive status 0.80 0.64 0.40
Instruction Condition (device) Processing time (s)
Q00JCPU Q00CPU Q01CPU

Table of Contents