EasyManua.ls Logo

Moeller DF51 - Maintenance and Inspection; General

Moeller DF51
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
07/04 AWB8230-1540GB
187
8 Maintenance and inspection
General
Frequency inverters are electronic devices. Maintenance work is
therefore not usually required. Local conditions and company
procedures may require regular inspection.
In general we recommend the following regular checks:
Electrocution hazard
The work described below must be performed only by
electricians and other suitably trained personnel.
Open the device only when it is safely isolated from its
supply and at zero volts!
After disconnecting the power supply, wait for at least
5 minutes before carrying out any maintenance,
installation or repair work to allow the capacitors to
discharge to harmless values.
Item Inspect for... Interval Method Values, remedies Own measures
Environment Extreme temperatures and
humidity
Monthly Thermometer,
hygrometer
Ambient temperature
between –10 to +40
o
C,
non-condensing
Mounting location Noise and vibration Monthly Visual and acoustic
check
Compatibility with the
environment for electrical
controllers.
Mains power
supply
Voltage fluctuations Monthly Measure voltage
between terminals
L1 and N or between
L1, L2 and L3
DF51-320, DF51-322:
200 to 240 V 50/60 Hz
DF51-340:
380 to 460 V 50/60 Hz
Insulation Sufficient resistance Annually Measure resistance
between PE and
terminals
At least 5 MO
Installation Firmness of screws Annually Torque spanner M3: 0.5 to 0.6 Nm
M4: 0.98 to 1.3 Nm
M5: 1.5 to 2 Nm
Power section
terminals
Secure connections Annually Visual inspection No abnormalities
Components
(general)
Overheating Annually Overtemperature
signal
Ambient temperature,
mounting position, fan:
no tripping
Capacitors Leakage, deformation Monthly Visual inspection No abnormalities
Resistors Cracks, discolouration Annually Visual inspection Resistance measurement
Fan Vibration, unusual noise,
dust
Monthly Visual inspection,
function test
Remove dust, rotate by
hand
Enclosure Dirt, dust, mechanical
damage
Annually Visual inspection Remove dirt and dust,
replace if damaged
General Odour, discolouration,
corrosion
Annually Visual inspection Normal appearance,
inspection of general
ambient conditions for
electronic devices
Displays, LEDs Legibility Monthly Visual inspection Correct function of all
LED segments

Table of Contents