10/05 AWB8230-1541GB
Motor control
93
Changing over time ramps
During operation, you can change over from the time ramps set
under PNU F002 and F003 to those programmed under PNU A092
and A093. This can be done either by applying an external signal
to digital input 2CH at any time or when the frequencies
configured under PNU A095 and A096 are reached.
Use PNU A094 to set the changeover mode.
X Use PNU A095 to define the required output frequency for
automatic changeover.
X Configure one of the digital inputs as 2CH by entering the value
09 in the corresponding PNU C001 to CC005.
The deceleration time is set with PNU A093 and A096.
Figure 91: Frequency-controlled acceleration ramp changeover
t
A095
A094 = 01
f
f
max
F002 A092
Figure 92: Contact-controlled changeover of acceleration ramps
Figure 93: Digital input 5 = 2CH (second time ramp)
t
A094 = 00
f
f
max
F002 A092
2CH
2CH
FWD
REV
P24125
PNU Name RUN b031
= 10
Value Function DS
A092 Acceleration
time 2
j j 0.01 – 3000 s Setting times for the second acceleration and deceleration time
0.1 to 999.9 s; resolution: 0.1 s
1000 to 3000 s; resolution: 1 s
15.00
A292
A093 Deceleration
time 2
A293
A094 Acceleration
time, specify
signal for
changeover
from
acceleration
time 1 to
acceleration
time 2
– – 00 Digital input (2CH) 00
01 Frequency (PNU A095 or A096)
A294
A095 Acceleration
time, frequency
for changeover
from ramp time
1 to ramp time
2
– – 0.0 – 400 Hz Here, set a frequency at which the changeover from the first to the
second acceleration time is to take place.
0.0
A295