Setting parameters
10/05 AWB8230-1541GB
92
Potentiometer (keypad)
Reference value input through the built-in potentiometer.
The manipulating range can be specifically matched with
parameters PNU A151 to A155, which are described below. You
can assign the frequency inverter’s output frequency to any
potentiometer position. To enable the potentiometer, enter value
00 in PNU A001.
To define the potentiometer’s function, use the following
parameters:
Figure 89: Keypad
A
RUN
PRG
Hz
PRG
EN
TER
I
O
POWER
ALARM
Figure 90: Setting range of keypad’s potentiometers
0 % 100 %
f
[Hz]
A154A153
A151
A152
A155 = 00
f
max
A004
A155 = 01
PNU Name RUN b031
= 10
Value Function DS
A001 Reference
value source
selection
00 Potentiometer (keypad) 01
A201 01 Analog input: Control signal terminals O and OI
02 Digital input (function PNU F001 or A020) and keypad
03 Serial interface (Modbus)
10 Calculator (calculated value of CAL)
A151 Potentiometer
(keypad),
starting
frequency
j 0 – 400 Hz The starting frequency output when the potentiometer is set to its left
stop.
0.0
A152 Potentiometer
(keypad), end
frequency
j 0 – 400 Hz The maximum frequency output when the potentiometer is set to its
right stop.
0.0
A153 Potentiometer
(keypad),
starting point
j 0 – 100 % The starting point (offset) for the potentiometer’s setting range. 0
A154 Potentiometer
(keypad), end
point
j 0 – 100 % The end point (offset) for the potentiometer’s setting range. 100
A155 Potentiometer
(keypad),
starting
frequency
source
j 00 Value from PNU A151 01
01 0Hz
These functions are enabled only if parameters PNU A151 and A153 contain a value above
zero.