Using the DF51
10/05 AWB8230-1541GB
54
Default functions of output terminals
By default, the control signal outputs have the functions described
below.
Table 16: Function of control signal terminals (outputs)
Figure 54: Active outputs with default settings
a Frequency indication, 0 to 10 V = 0 to 50 Hz
b AL fault message
c FA1 = frequency reached (reference value = actual value)
RUN = Run signal
a
b
c
0...10 V = 0...50 Hz
0 V
AMK14K11 K12
12 11 P24
+24 V
RUNFA1
L
CM2
h
Relay for direct connection to the digital outputs as shown
in Figure 54, for example ETS-VS3.
No. Function Value DS Technical data, description
P24 Control voltage
output
+24 V – Supply voltage
Load carrying capacity: 30 mA
Reference potential: terminal L
12 Transistor output
Up to 27 V = CM2 00 = RUN: Run signal Configurable, open collector
Load carrying capacity: up to 50 mA each
11 Transistor output 01 = FA1: Frequency achieved
CM2 Reference potential,
transistor output
0V
+24 V
– Common reference potential for transistor outputs
11 and 12; max. load carrying capacity 100 mA
(total of terminals 11 and 12)
“Sink-type logic” connection: reference potential
0V
“Source-type logic” connection: reference
potential +24 V (a page48)
L Common reference
potential
0 V – Reference potential (0 V) for internal voltage
source P24 and H, for analog inputs O and OI, and
for analog output AM.
AM Analog output 0 to +9.6 V Frequency actual value
(0 to 50 Hz)
Configurable DC voltage output, 10 V corresponds
with the set maximum frequency (50 Hz).
Accuracy: g5 % from target value
Load carrying capacity: 1 mA
Reference potential: terminal L
K11 Relay contact
• Up to 250 V AC/2.5 A
• Up to 30 V DC/3.0 A
05 = AL: Fault signal • Operating signal: K11-K14 closed.
• Fault message or power supply off: K11-K12
closed
K12 Break contact
K14 Make contact