Setting parameters
10/05 AWB8230-1541GB
114
Overload signal (OL)
The overload signal (OL) is output when the current value set with
PNU C041 is exceeded.
X To configure digital output 11 or 12 or signalling relay K1 as OL,
define the current under PNU C041 at which, when exceeded,
the OL signal is activated.
X Then configure one of the outputs 11 or 12 as OL by entering
the value 03 under PNU C021 or C022, or under PNU C026 for
signalling relay K1.
Figure 117:Function chart for OL (overload signal)
I
M
: Motor current
OL
I
M
C041
Figure 118:Digital output 11 configured as an OL (overload signal)
OL
24 V
50 mA
1112CM2
PNU Name RUN b031
= 10
Value Function DS
C041 Output
function –
warning
threshold for
overload signal
(OL)
– j 0 – 2 x Ie [A]
Default,
dependent on
frequency
inverter’s rated
current (Ie)
The current value entered here determines when the OL signal should
be activated.
Ie
1)
C241
1) Frequency inverter rated current