Setting parameters
10/05 AWB8230-1541GB
86
Specifying reference frequencies
The setpoint frequency can be assigned in one of three ways,
depending on the setting under PNU A01:
• through the LCD keypad’s potentiometer;
• through analog inputs O (0 to +10 V H) and/or OI (4 to 20 mA
H);
• through digital channels (PNU F001, fixed frequency CF1 to
CF15 or Modbus).
The reference source is selected with PNU A001.
Thermal overload, characteristic (torque curve) b013 b213 –
Motor current limitation – function b021 b221 –
Tripping current for motor current limitation b022 b222 –
Motor current limitation, deceleration time constant b023 b223 –
Motor current limitation, limit current selection b028 b228 –
Digital input 1 – function
C001 C201 –
Digital input 2 – function
C002 C202 –
Digital input 3 – function C003 C203 –
Digital input 4 – function C004 C204 –
Digital input 5 – function C005 C205 –
Output function – warning threshold for overload signal (OL) C041 C241 –
Motor – assigned rating [kW]/{HP} at rated voltage (Ue) H003 H203
Motor – number of poles H004 H204
Motor – stabilization constant
H006 H206
Motor – voltage class H007 H207
Description of the function
Parameter number (PNU)
Default Second parameter set
(STOP)
1)
SET (STOP)
1)
SP-SET (RUN)
2)
1) (STOP): Parameters or functions can be activated only in motor stop.
2) (STOP): Parameters or functions can be activated during operation.
h
Fixed frequency stage 0 (none of the inputs CF1 to CF4 are
activated) corresponds to the frequency setpoint
value.Depending on the value entered in PNU A001, this
can be defined with the installed potentiometer, the
setpoint value inputs O, O2 and/or OI or through
PNU F001 and PNU A020.
h
If one or more of the fixed frequencies exceeds 50 Hz, you
must first increase the maximum frequency with
PNU A004 (a section “End frequency”, page 66).