Setting parameters
10/05 AWB8230-1541GB
104
Analog output (AM)
The AM terminal provides the output frequency or the motor
current as voltage signal (0 to +10 V). The reference potential is
0 V (terminal L).
The selection between the frequency and motor current indication
is made with PNU C028.
Analog output signal
For signal compensation, PNU b080 (gain) and PNU C086 (offset)
are used. The signal accuracy after compensation is about g5%.
Figure 103:Analog output AM
0 – 10 V
1 mA
AML
–
+
Figure 104:Analog output signal
10 V
5 V
0 50 % 100 %
b080 = 50 %
C086
b080 = 100 %
b080 = 200 %
U
Hz
A
PNU Name RUN b031
= 10
Value Function DS
b080 Analog output
AM, gain factor
j j 0 – 255 Here the analog 0–10 V signal output at the AM terminal can be
compensated and matched to the frequency actual value or the output
current.
100
b086 Frequency
indication
scaling factor
for value in
PNU d007
j j 0.1 – 99.9 The product of the value displayed under PNU d001 and this factor is
displayed at PNU d007. This value is also available at the AM terminal.
1.0
C028 Analog output
AM, measured
value
indication
selection
– – 00 f-Out: Current output frequency: Indicates the output frequency in the
range 0 to f
max
(PNU A004)
00
01 I-Out: Current output current: Indicates the motor current in the range
0 to 200 %)
C086 Analog output
AM – offset
compensation
j j 0 – 10 V Offset compensation for analog output signal AM. 0.0