10/05 AWB8230-1541GB
Table for user-defined
parameter settings
229
C077
–
j Communication – set
monitoring time (watchdog).
0 – 99.99 s 0.00 150
C078
–
j Communication – waiting time
(latency between request and
response)
0 – 1000 ms 0 150
C081 jjAnalog input O – reference
value signal compensation
0 – 200 % 100 70
C082 jjAnalog input OI – reference
value signal compensation
0 – 200 % 100 70
C085 jjThermistor compensation
(digital input 5)
0 – 200 % 100 116
C086 jjAnalog output AM – offset
compensation
0 – 10 V 0.0 104
C091 jjDebug mode, view additional
parameters
00: Do not show parameter 00 146
01: Show parameter
C101
–
j Motor potentiometer –
reference value for motor
potentiometer after power
supply interruption
00: Clear last value and use default for
PNU F001
00 100
01: Use saved motor potentiometer value
set with UP/DWN function through
digital inputs.
C102
–
j Reset function (RST) – response
to a Reset signal
00: On a rising edge the fault signal is reset
and the motor is stopped.
00 122
01: On a falling edge the fault signal is
reset and the motor is stopped.
02: On a rising edge the fault message is
reset.
PNU RUN b031
= 10
Name Value range DS page User setting