Moeller DF51 - Signalling Relay K1 (Terminals K11, K12, K14)

Moeller DF51
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10/05 AWB8230-1541GB
Actual value and status signals
107
Signalling relay K1 (terminals K11, K12, K14)
At zero voltage, contacts K11-K12 are closed. When the supply
voltage is applied, signalling relay K1 is activated (K11-K14).
By default, the signalling relay is switched off when a fault occurs.
With PNU C026 you can change the assigned signal. The relay
contact (changeover contact) can be connected directly into
control circuits (24 V H 230 V ~) (a section “Connecting a
signalling relay”, page 41).
Table 34: Default setting of the signalling relay
h
Signalling relay K1 closes when supply voltage is applied
to contact K11-K12. When a fault occurs, this contact
opens. Fault signals must be reset with the Reset
command (RST) or with a disconnection of the supply
voltage.
Figure 108:Signalling relay K1
I
O
K12
K14
K11
AM
H
O
OI
L
L 5
4 3 2 1
P24
CM2
12 11
Default setting of the signalling relay Reconfigured signalling relay terminals (PNU 036 = 00)
Fault or DF51 switched off Run signal Fault message Run signal or DF51 switched off
Voltage Operating
state
K11-K12 K11-K14 Voltage Operating
state
K11-K12 K11-K14
On Normal Open Closed On Normal Closed Open
On Fault Closed Open On Fault Open Closed
Off Closed Open Off Closed Open
K12K11 K14
K12K11 K14 K12K11 K14
K12K11 K14