10/05 AWB8230-1541GB
Cables and fuses
207
Cables and fuses
The cross-sections of the cables and line protection fuses used
must correspond with local standards.
For supply voltage and motor cables which exceed about 20 m in
length, use cables with a larger cross-section.
Control cables should be screened and have a maximum cross-
section of 0.75 mm
2
.
For the cable which is to be connected to the signal output, use a
cable cross-section of 0.75 mm
2
.Strip about 5 to 6 mm off the
cable ends. The external diameter of the signal cable should be no
more than 2 mm, except for the connection to the signalling relay.
DF51- Connection to
power supply
L1, L2, L3, N, U, V, W,
PE (2x)
VDE UL
1)
Moeller mm
2
AWG
320-4K0 3-phase 230 V AC 35 A 30 A PKZM0-32 4.0 12
320-5K5
35 A 40 A PKZM0-40 6.0 10
320-7K5
50 A 50 A PKZM0-50 10 8
322-025 1/3-phase 230 V
AC
10 A 10 A FAZ-B10/1N, PKM0-10 1.5 16
322-037 1/3-phase 230 V
AC
10 A 10 A FAZ-B10/1N, PKM0-10 1.5 16
322-055 1/3-phase 230 V
AC
10 A 10 A FAZ-B10/1N, PKM0-10 1.5 16
322-075 1/3-phase 230 V
AC
16 A 15 A FAZ-B16/1N, PKM0-16 2.5 14
322-1K1 1/3-phase 230 V
AC
20 A 15 A FAZ-B16/1N, PKM0-16 2.5 14
322-1K5 Single-phase 230 V 25 A 25 A FAZ-B20/1N 4.0 12
3-phase 230 V AC 16 A 15 A PKM0-16 4.0 12
322-2K2 Single-phase 230 V 30 A 30 A FAZ-B32/1N 6.0 10
3-phase 230 V AC 20 A 20 A PKM0-20 6.0 10
340-037 3 AC 400 V 4 A 3 A PKM0-4 1.5 16
340-075
6 A 6 A PKM0-6.3 1.5 16
340-1K5 10 A 10 A PKM0-10 1.5 16
340-2K2
10 A 10 A PKM0-10 1.5 16
340-3K0
16 A 15 A PKM0-16 2.5 14
340-4K0 16 A 15 A PKM0-16 2.5 14
340-5K5 20 A 20 A PKM0-20 4.0 12
340-7K5 25 A 25 A PKM0-25 4.0 12
1) Tripping characteristic UL-rated, class J, 600 V
(approved fuses and fuse holders)