Actual value and status signals
109
RUN signal
The RUN signal is issued when an enable signal (FWD/REV) is
applied. With the set deceleration ramp, the RUN signal remains
active until the output frequency has reached 0 Hz.
By default, RUN is assigned to digital output 12.
X Configure one of the digital outputs 11 or 12 as RUN by
entering the value 00 under PNU C021 or C022, or under
PNU C026 for signalling relay K1.
Figure 109:Function chart for RUN “operational”
f
2
: Output frequency
FWD/REV
RUN
f
2
Figure 110:Digital output 12 configured as RUN (Run signal)
RUN
24 V
50 mA
12CM2
PNU Name RUN b031
= 10
Value Function DS
b082 Increased
starting
frequency
(e.g. with high
level of friction)
j 0.5 – 9.9 Hz A higher starting frequency results in shorter acceleration and
deceleration times (for example to overcome high frictional resistance).
If the frequencies are too high, fault message E002 may be issued. Up
to the set starting frequency, the motor accelerates without a ramp
function.
0.5