Appendix
10/05 AWB8230-1541GB
224
b022
–
j Tripping current for motor
current limitation
0.2 – 1.5 x I
e
[A]
Default,
dependent on frequency inverter’s rated
current (I
e
)
I
e
x 1.5 113
b222
–
j Motor current limitation,
tripping current
(second parameter set)
Values a PNU b022 I
e
x 1.5 113
b023
–
j Motor current limitation,
deceleration time constant
0.1 – 3000 s 1.0 113
b223
–
j Motor current limitation,
deceleration time constant
(second parameter set)
0.1 – 3000 s 1.0 113
b028
–
j Motor current limitation, limit
current selection
00: Value of PNU b022 00 113
01: Analog input O-L
b228
–
j Motor current limitation, limit
current selection
(second parameter set)
00: Value of PNU b222 00 113
01: Analog input O-L
b031
–
j Parameter access inhibit
(access rights)
00: Access to all parameters except
PNU b031 disabled when digital input
SFT is enabled (a PNU C001: 15)
01 143
01: Access to all parameters except
PNU b031 and F001 (A020, A220,
A021 to A035, A038) disabled when
digital input SFT is enabled
(a PNU C001: 15)
02: Access to all parameters except
PNU b031 disabled
03: Access rights to all parameters except
PNU b031 and F001 (A020, A220,
A021 to A035, A038) disabled
10: Extended access rights to parameters in
RUN mode.
b080 jjAnalog output AM, gain factor 0 – 255 100 104
b082
–
j Increased starting frequency
(e.g. with high level of friction)
0.5 – 9.9 Hz 0.5 109
b083
––
Carrier frequency 2 – 14 kHz 5.0 141
b084
––
Initializing – function 00: Clear fault register 00 144
01: Load default settings (DS)
02: Clear fault register and load default
settings (DS)
b085
––
Initialization, country-specific
default settings
00: Japan 01 {02} 144
01: Europe
02: USA
b086 jjFrequency indication scaling
factor for value in PNU d007
0.1 – 99.9 1.0 104
b087
–
j STOP button (keypad) 00: Enabled 00 140
01: Disabled
PNU RUN b031
= 10
Name Value range DS page User setting