10/05 AWB8230-1541GB
Table for user-defined
parameter settings
225
b088
–
j Motor restart after removal of
the FRS signal
00: Restart with 0 Hz 00 79
01: Restart with the determined output
frequency (current motor speed)
b089 j j Indication, value on mains
operation (RS 485)
01: Output frequency (d001) 01 ###
02: Output current (d002)
03: Direction of rotation (d003)
04: Actual value (PV) (d004)
05: State of digital inputs (d005)
06: State of digital outputs (d006)
07: Scaled output frequency (d007)
b091
––
STOP key, (keypad), selection of
motor stop on actuation
00: DEC, braking to 0 Hz with deceleration
ramp
00 140
01: FRS, free coasting down to 0 Hz
b130
–
j Internal DC link, stop
deceleration ramp on
overvoltage in the internal DC
link
00: OFF, disabled 00 141
01: ON, enabled
b131 jjDeceleration ramp, switching
threshold dependent on
internal DC link voltage
330 – 395 V (U
e
= 230 V) 380/
760 141
660 – 790 V (U
e
=400V)
Default, dependent on rated voltage (U
e
)
b150
–
j Pulse frequency, automatic
pulse frequency reduction on
overtemperature
00: OFF, disabled 00 141
01: ON, enabled
b151 jjInverter, reduce inverter’s
response time (RDY) to a
control signal
00: OFF 00 142
01: ON
PNU RUN b031
= 10
Name Value range DS page User setting