10/05 AWB8230-1541GB
Motor control
69
Reference and control signal inputs
Microswitch 485/OPE configures the serial interface (RJ 45
communication interface):
Microswitch TM/PRG selects the source of the reference value and
control signal input.
By default (PNU A001 = 01 and A002 = 01), the position of
microswitch TM/PRG is ignored for the purpose of reference value
and control signal input.
Figure 72: Microswitches
SR
SK
485
OPE
TM
PRG
I
O
K12 K14 K11
AM
H
O
OI
L
L 5
4 3 2 1
P24
CM2
12 11
h
Reference value and control signal inputs depend on
PNU A001 and A002 and the position of microswitches
485/OPE and TM/PRG.
Position
485/OPE
Description Reference and control
signal input
485 (RS 485) Serial interface Keypad DEX-KEY-6
Keypad DEX-KEY-61
Modbus RTU (network)
OPE
(operator)
Manual operation
(point-to-point
connection)
Keypad DEX-KEY-6
1)
Keypad DEX-KEY-611
)
Keypad DEX-KEY-101
)
Parameterization software
Drive Soft
1) To ensure unrestricted communications, set the switch to position
485.
Position
TM/PRG
Description Reference and control
signal input
PRG
(program)
Reference input for
output frequency
Specification according to
setting under PNU A001
Start (RUN) signal
input
Specification according to
setting under PNU A002
TM (terminal
= control
signal
terminals)
Reference input for
output frequency
Analog input O or OI
Start (RUN) signal
input
Digital inputs FWD and/or
REV