Setting parameters
10/05 AWB8230-1541GB
72
Basic parameters
Input/indication of reference frequency
PNU F01
indicates the current reference frequency or the current fixed
frequency. You can change the frequencies with the arrow keys
and save the settings as defined with PNU A01 and the fixed
frequency stages CF1 to CF4 (digital inputs) (a section “Fixed
frequencies”, page 97).
With PNU F01, you can change the reference value even when
parameter protection has been set with PNU b31.
If you have not activated any fixed frequencies, PNU F01 indicates
the set reference frequency.
If you specify the setpoint frequency with PNU A020, you can
enter a new value under PNU F001, which is saved automatically
in PNU A020:
X Change the current value with the arrow keys.
X Save the modified value with the ENTER key.
The saved value is automatically written to PNU A020.
h
Micro switch TM/PRG must be in the TM position.
Figure 74: Microswitch
SR
SK
485
OPE
TM
PRG
P24
CM2
12
11
PNU Name RUN b031
= 10
Value Function DS
A001 Reference
value source
selection
– – 00 The setting range is limited by PNU b082 (raised starting frequency) and
A004 (maximum frequency).
• Potentiometer (keypad)
•Frequency [Hz]
• Process variable [%] with active PID control (PNU A071 = 1)
01
01 Analog input: Control signal terminals O and OI
02 Set value (PNU F001) of the keypad (arrow keys Í/Ú). To save the set
value, press the ENTER key (PNU A020).
03 Serial interface (Modbus)
10 Calculator: Calculated value (CAL) (a section “Mathematical
functions”, page 127).
F001 Reference
value, input
through
keypad
j j Frequency: 0.0
– 400 Hz
(0.1 Hz)
Resolution g0.1 Hz
The reference value can be defined using various methods:
• With PNU F001 or A020: Enter the value 02 under PNU A001.
• With the potentiometer on the keypad: Enter the value 00 under
PNU A01.
• With a 0 to 10 V voltage signal or a 4 to 20 mA current signal at
analog input O or OI: Enter the value 01 under PNU A01.
• With the digital inputs configured as CF1 to CF4. After selection of
the required fixed frequency stage using CF1 to CF4, the frequency
for the respective stage can be entered.
The display of the reference value is independent of which method was
used to set the reference value.
0.0