10/05 AWB8230-1541GB
Table for user-defined
parameter settings
231
d003 jjDirection of rotation display F: Clockwise (forward) rotating field
O: STOP
R: Anticlockwise (reverse) rotating field
–57
d004 jjPID feedback display 0.00 – 99.99 (0.01 %)
100.0 – 999.9 (0.1 %)
1000 – 9999 (1 %)
57, 132
d005 jjIndication – status of digital
inputs 1 to 5
––57
d006 jjIndication – status of digital
outputs 11 and 12, and relay K1
––57
d007 jjIndication of scaled output
frequency
0.00 – 9999 (0.01/0.1/1/10 Hz) 57
d013 jjIndication – output voltage 0 – 600 V (1 V) 57
d016 jjIndication – operation time
counter
0 – 9999 (1 h)
10000 – 99990 (10 h)
100000 – 999000 (1000 h)
–57
d017 jjIndication – mains On time 0 – 9999 (1 h)
10000 – 99990 (10 h)
100000 – 999000 (1000 h)
–57
d080 jjIndication – total number of
occurred faults
0 – 65530 57
d081 jjIndication – fault 1 (last fault
signal)
Values at time of power Off:
Fault signal E…
•Frequency (Hz)
Current (A)
Internal DC link voltage (VDc)
Total operating hours in RUN mode
Total Power On time, power supply
connected (h)
–57
d082 jjIndication – fault 2 Values a PNU d081 57
d083 jjIndication – fault 3 Values a PNU d081 57
PNU RUN b031
= 10
Name Value range DS page Reference
value
F001 jjReference value, input through
keypad
Frequency: 0.0 – 400 Hz (0.1 Hz)
Process variable 0.00 to 9999 % with PID
control enabled (A071 = 01) with display
factor (A075).
0.0 87
F002 jjAcceleration time 1 0.01 – 99.99 (0.01 s)
100.0 – 999.9 (0.1 s)
1000 – 3000 (1 s)
10.00 73
F202 jjAcceleration time 1
(second parameter set)
Values a PNU F002 10.00 73
F003 jjDeceleration time 1 0.01 – 99.99 (0.01 s)
100.0 – 999.9 (0.1 s)
1000 – 3000 (1 s)
10.00 73
F203 jjDeceleration time 1
(second parameter set)
Values a PNU F003 10.00 73
F004 jjDirection of rotation – function
of START key (keypad)
00: Clockwise rotating field ( FWD)
01: Anticlockwise rotating field (REV)
00 73
PNU RUN b031
= 10
Name Value range DS page