Appendix
10/05 AWB8230-1541GB
230
C141
––
Logic function – select input A 00: RUN: In operation 00 130
01: FA1: Frequency reference value reached
02: FA2: Frequency signal – output
frequency exceeds value in PNU C042
(during acceleration ramp) or
PNU C043 (during deceleration ramp)
03: OL: Overload warning – motor current
exceeds value in PNU C041.
04: OD: PID control – reference/actual
value difference exceeds signalling
threshold set with PNU C044.
05: AL: Fault – fault/alarm signal
06: Dc: Warning – Reference value at input
O (0 to +10 V) lower than value in
PNU b082 or current signal at input OI
below 4 mA.
07: FBV: PID control – Actual value
monitoring (PV) signal on breach of
limit values PNU C052/C053.
08: NDc: Fault/warning dependent on
PNU C077 – communication watchdog
timer has expired: communications are
faulty.
10: ODc: Fault/warning – communication
overload or interrupted (with optional
DE51-NET-CAN, DE51-NET-DP).
C142
––
Logic function – select input B Values a PNU C141 01 130
C143
––
Logic function – select link
[LOG]
00: [LOG] = A AND B 00 130
01: [LOG] = A OR B
02: [LOG] = A XOR B
C144
–
j Digital output 11 – deceleration
time (On)
0 – 100 s 0.0 106
C145
–
j Digital output 11 – deceleration
time (Off)
0 – 100 s 0.0 106
C146
–
j Digital output 12 – deceleration
time (On)
0 – 100 s 0.0 106
C147
–
j Digital output 12 – deceleration
time (Off)
0 – 100 s 0.0 106
C148
–
j Relay K1 – deceleration time
(On)
0 – 100 s 0.0 108
C149
–
j Relay K1 – deceleration time
(Off)
0 – 100 s 0.0 108
PNU RUN b031
= 10
Name Value range DS page User setting
PNU RUN b031
= 10
Name Value range DS page
d001 jjOutput frequency display 0.0 – 400.0 Hz (0.1 Hz) – 57
d002 jjOutput current display 0.0 – 999.9 A (0.1 A) – 57