Setting parameters
10/05 AWB8230-1541GB
108
Table 35: Functions of the signalling relay
Response time
You can set the response time of signalling relay K1 between 0 and
100 s. The On- and off-delay can be adjusted separately.
PNU Name RUN b031
= 10
Value Function DS
C026 Relay K1 –
signal
– – 00 RUN: In operation 05
01 FA1: Frequency reference value reached
02 FA2: Frequency signal – output frequency exceeds value in PNU C042
(during acceleration ramp) or PNU C043 (during deceleration ramp)
03 OL: Overload warning – motor current exceeds value in PNU C041.
04 OD: PID control – reference/actual value difference exceeds signalling
threshold set with PNU C044.
05 AL: Fault – fault/alarm signal
06 Dc: Warning – Reference value at input O (0 to +10 V) lower than value
in PNU b082 or current signal at input OI below 4 mA. (reference value
signal interrupted)
07 FBV: PID control – Actual value monitoring (PV) signal on breach of limit
values PNU C052/C053. (actual value signal interrupted)
08 NDc: Fault/warning dependent on PNU C077 – communication
watchdog timer has expired: communications are faulty.
09 LOG: Shows result of logic link performed through PNU C143. (High,
Low)
10 ODc: Fault/warning – communication overload or interrupted (with
optional DE51-NET-CAN, DE51-NET-DP).
C036 Relay K1 (K11-
K12) – logic
– – 00 Normally open contact (NO) 01
01 Normally closed contact (NC)
PNU Name RUN b031
= 10
Value Function DS
C148 Relay K1 –
deceleration
time (On)
– – 0 – 100 s Delay on energization 0.0
C149 Relay K1 –
deceleration
time (Off)
– – 0 – 100 s Delay on power off 0.0
a figure 107, page 106