Appendix
10/05 AWB8230-1541GB
190
Specific technical data of the DF51-322
The table below contains the specific technical specifications of
the single- and three-phase 230 V series, such as current, voltage,
and torque values.
Frequency and current monitoring Connection of an analog display device: 0 to 10 VH, up to 1 mA for frequency or current
Connection of a digital frequency meter
Signalling relay Relay contacts as two-way switch
Further features (not a complete listing) Automatic voltage regulation
Unattended start protection
Variable amplification and output voltage reduction
•Frequency jumps
Minimum/maximum frequency limitation
Output frequency display
Fault register available
Freely selectable pulse frequency: 2 to 14 kHz
PID control
Automatic torque boost
Second parameter set selectable
Safety features
Overcurrent
Overvoltage
Undervoltage
Overtemperature
Earth fault (on Power On)
Overload
Electronic motor protection
Current transformer fault
Ambient conditions
Ambient temperature –10 to +50 °C
From about +40 to +50 °C, the pulse frequency should be reduced to 2 kHz. The output
current should be less than 80 % of the rated current in this case.
Temperature/humidity during storage
–25 to 70 °C (for short periods only, for example during transport)
20 to 90 % relative humidity (non condensing)
Permissible vibration
Maximum 5.9 m/s
2
(= 0.6 g) at 10 to 55 Hz
Installation height and location
Maximum 1000 m above sea level in a housing or control panel (IP 54 or similar)
Optional accessories
Remote operating units DEX-KEY-10, DEX-KEY-6, DEX-KEY-61
Line reactor to improve the power factor
RFI filter
Motor reactor
Sine-wave filter
Field bus interface module CANopen (DE51-NET-CAN)
DF51
DF51-322-… 025 037 055 075 1K1 1K5 2K2
Maximum permissible active power of motor in kW; data for
four-pole three-phase asynchronous motors
0.25 0.37 0.55 0.75 1.1 1.5 2.2
Maximum permissible apparent motor
power in kVA
230 V
0.5 1.0 1.1 1.5 1.9 2.8 3.9
240 V 0.5 1.0 1.2 1.6 2.0 2.9 4.1
1) If the regenerative braking torque is high, an external braking device with braking
resistor must be used. Alternatively, you can use a DV51 with external braking
resistor and – if required – optional keypad DEX-KEY-6… instead of the DF51. On
the DV51 the braking device function is built in.