Appendix
10/05 AWB8230-1541GB
210
Mains contactors
h
The mains contactors listed here assume the network’s
rated current (I
LN
) without mains choke or mains filter.
Their selection is based on the thermal current (AC-1).
Caution!
Jog mode must not be used through the mains contactor
(rest period f 180 s between switching off and on)
h
For single-phase mains connection, the use of paralleling
link DILM12-XP1 is recommended to ensure even loading
of all contact decks.
Figure 185:Mains contactor at single-phase connection
DILM12-XP1
DILM
DILM12-XP1
2
35
4
6
A1
A2
1
13
14
DF51- DF51 phase current Mains contactor DF51 starting current (RC
load current at maximum
input voltage)
Conventional thermal
current I
th
=I
e
AC-1 at
60 %, open
Type
I
LN
[A] I
th
AC-1 [A] I
0
[A]
Connection 1 ~ 230 V (240 V g 10 %)
322-025 3.5 20 DILM7 31.9
322-037 5.8
322-055 6.7
322-075 9
322-1K1 11.2
322-1K5 17.2
322-2K2 24
DILM7 + DILM12-XP1
1)
1) For single-phase line connection of the DF51-322-2K2, all
three contacts must be connected through paralleling link
DILM12-SP1.
Connection 3 ~ 230 V (240 V g 10 %)
320-4K0 22 35 DILM17 31.9
320-5K5 30
35 DILM17
320-7K5 40
40 DILM25 16
322-025 2 20 DILM7 31.9
322-037 3.4
322-055 3.9
322-075 5.2
322-1K1 6.5
322-1K5 10
322-2K2 14