10/05 AWB8230-1541GB
Table for user-defined
parameter settings
227
C002
––
Digital input 2 – function Values a PNU C001 01 77
C202
––
Digital input 2 – function
(second parameter set)
Values a PNU C001 01 77
C003
––
Digital input 3 – function Values a PNU C001 02 {16} 77
C203
––
Digital input 3 – function
(second parameter set)
Values a PNU C001 02 77
C004
––
Digital input 4 – function Values a PNU C001 03 {13} 77
C204
––
Digital input 4 – function
(second parameter set)
Values a PNU C001 03 77
C005
––
Digital input 5 – function Values a PNU C001 18 {09} 77
C205
––
Digital input 5 – function
(second parameter set)
Values a PNU C001 18 77
C011
––
Digital input 1 – logic 00: High signal triggers switching 00 78
01: Low signal triggers switching
C012
––
Digital input 2 – logic Values a PNU C011 00 78
C013
––
Digital input 3 – logic Values a PNU C011 00 78
C014
––
Digital input 4 – logic Values a PNU C011 00 78
C015
––
Digital input 5 – logic Values a PNU C011 00 78
C021
––
Digital output 11 – signal 00: RUN: In operation 01 105
01: FA1: Frequency reference value reached
02: FA2: Frequency signal – output
frequency exceeds value in PNU C042
(during acceleration ramp) or
PNU C043 (during deceleration ramp)
03: OL: Overload warning – motor current
exceeds value in PNU C041.
04: OD: PID control – reference/actual
value difference exceeds signalling
threshold set with PNU C044.
05: AL: Fault – fault/alarm signal
06: Dc: Warning – Reference value at input
O (0 to +10 V) lower than value in
PNU b082 or current signal at input OI
below 4 mA.
07: FBV: PID control – Actual value
monitoring (PV) signal on breach of
limit values PNU C052/C053.
08: NDc: Fault/warning dependent on
PNU C077 – communication watchdog
timer has expired: communications are
faulty.
09: LOG: Shows result of logic link
performed through PNU C143.
10: ODc: Fault/warning – communication
overload or interrupted (with optional
DE51-NET-CAN, DE51-NET-DP).
C022
––
Digital output 12 – signal Values a PNU C021 00 105
PNU RUN b031
= 10
Name Value range DS page User setting