Appendix
10/05 AWB8230-1541GB
228
C026
––
Relay K1 – signal Values a PNU C021 05 108
C028
––
Analog output AM, measured
value indication selection
00: f-Out: Current output frequency 00 104
01: I-Out: Current output current
C031
––
Digital output 11 – logic 00: Normally open contact (NO) 01, 00 106
01: Normally closed contact (NC)
C032
––
Digital output 12 – logic Values a PNU C031 01, 00 106
C036
––
Relay K1 (K11-K12) – logic Values a PNU C031 01 108
C041
–
j Output function – warning
threshold for overload signal (OL)
0 – 2 x I
e
[A]
Default, dependent on frequency inverter’s
rated current (I
e
)
I
e
114
C241
–
j Output function – warning
threshold for overload warning
(OL)
(second parameter set)
0 – 2 x I
e
[A]
Default, dependent on frequency inverter’s
rated current (I
e
)
I
e
114
C042
–
j Output function – signalling
threshold for frequency signal
FA2 during acceleration
0 – 400 Hz 0.0 111
C043
–
j Output function – signalling
threshold for frequency signal
FA2 during deceleration
0 – 400 Hz 0.0 111
C044
–
j Output function: Signalling
threshold, maximum PID
control deviation
0 – 100 % 3.0 136
C052
–
j PID controller – switch-off
threshold for second stage of PID
controller
0 – 100 % 100 139
C053
–
j PID controller – switch-on
threshold for second stage of PID
controller
0 – 100 % 0.0 139
C071
–
j Communication – baud rate 04 4800 bit/s 06 149
05: 9600 bit/s
06: 19200 bit/s
C072
–
j Communication – address 1 – 32 1 150
C074
–
j Communication – parity 00: None 00 150
01: Even
02: Odd
C075
–
j Communication – stop bits 1: 1 bit 1 150
2: 2 bits
C076
–
j Communication: Behaviour of
frequency inverter on
communication errors
00: Switch off on fault signal E60 02 150
01: Decelerate to standstill at deceleration
ramp and then switch off with error
E60.
02: No fault signal
03: FRS: Free run stop (free coasting,
= controller inhibit)
04: DEC: Braking to 0 Hz at set deceleration
ramp
PNU RUN b031
= 10
Name Value range DS page User setting