Setting parameters
10/05 AWB8230-1541GB
106
Configurable digital outputs 11 and 12 are by default configured
as N/O contacts. When an assigned function activates the output,
terminal CM2 is connected with terminal 11 or 12.
Optionally, you can configure the digital outputs as break (NC)
contacts. To do this, enter 01 under PNU C031 and C032
(corresponding to digital output 11 and 12).
Table 33: Configuration of digital outputs as break contacts
Response time of outputs
You can set the response time of digital outputs 11 and 12
between 0 and 100 s. The On- and off-delay can be adjusted
separately.
Example:
PNU Termina
l
Valu
e
Adjustable in
RUN mode
Function DS
C031 11 00 or
01
00: Make
contact
01: Break
contact
00
C032 12
Figure 107:Output signal
a Output signal without delay
b Output signal with on-delay
c Output signal with off-delay
d Output signal with on- and off-delay
e When the on signal is lower than the On-delay, the output is not
activated.
f The off-delay is activated regardless of the signal duration.
t
1
: On-delay
t
2
:Off-delay
t
t
1
t
1
t
2
t
2
t
1
a
b
c
d
t
2
f
e
PNU Name RUN b031
= 10
Value Function DS
C144 Digital
output 11 –
deceleration
time (On)
j 0 – 100 s Delay on energization 0.0
C145 Digital
output 11 –
deceleration
time (Off)
j 0 – 100 s Delay on power off 0.0
C146 Digital
output 12 –
deceleration
time (On)
j 0 – 100 s Delay on energization 0.0
C147 Digital
output 12 –
deceleration
time (Off)
j 0 – 100 s Delay on power off 0.0