Setting parameters
10/05 AWB8230-1541GB
130
You can assign the result of this logic link (LOG) to a digital output
with PNU C021, C022 or C026.
PNU Name RUN b031
= 10
Value Function DS
C141 Logic function
– select input A
– – 00 RUN: In operation 00
01 FA1: Frequency reference value reached
02 FA2: Frequency signal – output frequency exceeds value in PNU C042
(during acceleration ramp) or PNU C043 (during deceleration ramp)
03 OL: Overload warning – motor current exceeds value in PNU C041.
04 OD: PID control – reference/actual value difference exceeds signalling
threshold set with PNU C044.
05 AL: Fault – fault/alarm signal
06 Dc: Warning – Reference value at input O (0 to +10 V) lower than value
in PNU b082 or current signal at input OI below 4 mA.
07 FBV: PID control – Actual value monitoring (PV) signal on breach of limit
values PNU C052/C053.
08 NDc: Fault/warning dependent on PNU C077 – communication
watchdog timer has expired: communications are faulty.
10 ODc: Fault/warning – communication overload or interrupted (with
optional DE51-NET-CAN, DE51-NET-DP).
C142 Logic function
– select input B
– – 00 RUN: In operation 01
01 FA1: Frequency reference value reached
02 FA2: Frequency signal – output frequency exceeds value in PNU C042
(during acceleration ramp) or PNU C043 (during deceleration ramp)
03 OL: Overload warning – motor current exceeds value in PNU C041.
04 OD: PID control – reference/actual value difference exceeds signalling
threshold set with PNU C044.
05 AL: Fault – fault/alarm signal
06 Dc: Warning – Reference value at input O (0 to +10 V) lower than value
in PNU b082 or current signal at input OI below 4 mA.
07 FBV: PID control – Actual value monitoring (PV) signal on breach of limit
values PNU C052/C053.
08 NDc: Fault/warning dependent on PNU C077 – communication
watchdog timer has expired: communications are faulty.
10 ODc: Fault/warning – communication overload or interrupted (with
optional DE51-NET-CAN, DE51-NET-DP).
C143 Logic function
– select link
[LOG]
– – 00 [LOG] = A AND B, AND sequence 00
01 [LOG] = A OR B, OR sequence
02 [LOG] = A XOR B, Exclusive OR sequence