10/05 AWB8230-1541GB
Table for user-defined
parameter settings
223
PNU RUN b031
= 10
Name Value range DS page User setting
b001
–
j POWER, restarting mode after
power supply interruption
00: Fault signal E 09, automatic restart at
0Hz
00 117
01: Automatic restart at set starting
frequency after expiry of time set with
PNU b003.
02: After the time set with PNU b003 has
elapsed, the frequency inverter
synchronizes to the current motor
rotation speed and the motor is
accelerated to the current reference
value in the set ramp times.
03: After the time set under PNU b003 has
elapsed, the inverter synchronizes to
the current motor rotation speed and
the motor brakes to a stop in the set
deceleration time. A fault message is
then displayed.
b002
–
j POWER, permissible power
supply downtime
0.3 – 25 s 1.0 117
b003
–
j POWER, waiting time before
automatic restart after power
supply failure
0.3 – 100 s 1.0 79
b004
–
j POWER, fault signal on
intermittent supply voltage
failure or undervoltage
00: OFF, disabled 00 118
01: ON, enabled
b005
–
j POWER, number of automatic
restarting attempts after
intermittent supply voltage
failure or undervoltage
00: 16 restarts 00 118
01: No limit
b012
–
j Thermal overload, tripping
current
0.2 – 1.2 x I
e
[A]
Depending on frequency inverter’s rated
current (I
e
)
xx 115
b212
–
j Thermal overload, tripping
current (second parameter set)
0.2 – 1.2 x I
e
[A]
Default,
dependent on frequency inverter’s rated
current (I
e
)
xx (I
e
) 115
b013
–
j Thermal overload,
characteristic (torque curve)
00: Reduced torque 1 01 115
01: Constant torque
02: Reduced torque 2
b213
–
j Thermal overload,
characteristic (torque curve)
(second parameter set)
Values a PNU b013 01 115
b021
–
j Motor current limitation –
function
00: OFF, disabled 01 113
01: ON, enabled in acceleration phase and
at constant speed
02: Enabled only at constant speed
b221
–
j Motor current limitation,
function
(second parameter set)
Values a PNU b021 01 113