Setting parameters
10/05 AWB8230-1541GB
100
PNU Name RUN b031
= 10
Value Function DS
A001 Reference
value source
selection
– – 00 The setting range is limited by PNU b082 (raised starting frequency) and
A004 (maximum frequency).
• Potentiometer (keypad)
•Frequency [Hz]
• Process variable [%] with active PID control (PNU A071 = 1)
01
01 Analog input: Control signal terminals O and OI
02 Set value (PNU F001) of the keypad (arrow keys Í/Ú). To save the set
value, press the ENTER key (PNU A020).
03 Serial interface (Modbus)
10 Calculator: Calculated value (CAL) (a section “Mathematical
functions”, page 127).
C101 Motor
potentiometer
– reference
value for motor
potentiometer
after power
supply
interruption
– j 00 Clear last value and use default for PNU F001 00
01 Use saved motor potentiometer value set with UP/DWN function
through digital inputs.