Appendix
10/05 AWB8230-1541GB
220
A064
j Frequency jump (1) – jump
width
0 – 10 Hz 0.5 96
A065
j Frequency jump (2) 0 – 400 Hz 0.0 96
A066
j Frequency jump (2) – jump
width
0 – 10 Hz 0.5 96
A067
j Frequency jump (3) 0 – 400 Hz 0.0 96
A068
j Frequency jump (3) – jump
width
0 – 10 Hz 0.5 96
A071
j PID control 00: OFF, disabled 00 131
01: ON, enabled
A072 jjPID controller – P-component 0.2 – 5.0 0.1 131
A073 jjPID controller – I-component 0.0 – 150 s 0.1 131
A074 jjPID controller – D-component 0.00 – 100 s 0.01 131
A075
j PID control, display factor 0.01 – 99.99 1.00 131
A076
j PID controller – actual value
signal PV input
00: Analog input OI (4 20 mA) 00 131
01: Analog input O (0 10 V)
02: Serial interface (Modbus)
10: Calculated value (PNU A143)
A077
j PID control – invert input
signals
00: OFF, disabled, reference value (+),
actual value (–)
00 131
01: ON, enabled, reference value (–), actual
value (+)
A078
j PID controller – output signal
limit
0 – 100 % 0.0 132
A081
––
Output voltage (AVR function) 00: ON, enabled 00 67
01: OFF, disabled
02: DOFF, disabled during deceleration
A082
––
Output voltage (AVR motor
rated voltage)
DF51-32…-…: 200, 215, 220, 230, 240 230/400 67
DF51-340-…: 380, 400, 415, 440, 460, 480
Default setting depends on series
A092 jjAcceleration time 2 0.01 – 3000 s 15.00 93
A292 jjAcceleration time 2 (second
parameter set)
0.01 – 3000 s 15.00 93
A093 jjDeceleration time 2 0.01 – 3000 s 15.00 93
A293 jjDeceleration time 2
(second parameter set)
0.01 – 3000 s 15.00 93
A094
––
Acceleration time, specify
signal for changeover from
acceleration time 1 to
acceleration time 2
00: Digital input (2CH) 00 93
01: Frequency (PNU A095 or A096)
A294
––
Acceleration time, specify
signal for changeover from
acceleration time 1 to
acceleration time 2
(second parameter set)
00: Digital input (2CH) 00 93
01: Frequency (PNU A295 or A296)
PNU RUN b031
= 10
Name Value range DS page User setting

Table of Contents