10/05 AWB8230-1541GB
Table for user-defined
parameter settings
219
A038 jjJog mode –
jog mode reference value
0 – 9.99 Hz 1.00 101
A039
–
j Jog mode –
motor stop method
00: Free coasting 00 101
01: Deceleration ramp
02: DC braking
A041 jjBoost function 00: Manual 00 68
01: Automatic
A241 jjBoost function
(second parameter set)
Values a PNU A041 00 68
A042 jjBoost,
manual voltage boost
0 – 20 % 5.0 68
A242 jjBoost,
manual voltage boost
(second parameter set)
0 – 20 % 0.0 68
A043 jjBoost,
transition frequency for
maximum voltage boost
0 – 50 % 3.0 68
A243 jjBoost,
transition frequency for
maximum voltage boost
(second parameter set)
0 – 50 % 0.0 68
A044
A244
–
–
–
–
U/f characteristic
U/f characteristic
(second parameter set)
00: Constant torque curve 02
02
68
68
01: Reduced torque curve
Values a PNU A044
A045 – – U/f characteristic, output
voltage
20 – 100 % 100 68
A245 – – U/f characteristic, output
voltage
(second parameter set)
Values a PNU A045 100 68
A051
–
j DC braking 00: OFF, disabled 00 126
01: ON, enabled
A052
–
j DC braking – starting frequency 0 – 60 Hz 0.5 126
A053
–
j DC braking – waiting time 0 – 5 s 0.0 126
A054
–
j DC braking torque 0 – 100 % 0. 126
A055
–
j DC braking duration 0 – 60 s 0.0 126
A056
–
j DC braking – behaviour on
activation of the digital input
(DB)
00: Timed braking according to value of
PNU A055
01 126
01: Continuous operation
A061
–
j Maximum operating frequency 0 – 400 Hz 0.0 95
A261
–
j Maximum operating frequency
(second parameter set)
0 – 400 Hz 0.0 95
A062
–
j Minimum operating frequency 0 – 400 Hz 0.0 95
A262
–
j Minimum operating frequency
(second parameter set)
0 – 400 Hz 0.0 95
A063
–
j Frequency jump (1) 0 – 400 Hz 0.0 96
PNU RUN b031
= 10
Name Value range DS page User setting