Setting parameters
10/05 AWB8230-1541GB
126
PNU Name RUN b031
=10s
Value Function DS
A051 DC braking – j 00 OFF, disabled 00
01 ON, enabled
A052 DC braking –
starting
frequency
– j 0 – 60 Hz When PNU A51 is set to 01, DC braking is activated when the actual
frequency falls below the frequency entered here.
0.5
A053 DC braking –
waiting time
– j 0 – 5 s When the frequency set with PNU A052 is reached, the motor coasts for
the time duration entered here before DC braking is activated.
0.0
A054 DC braking
torque
– j 0 – 100 % Adjustment range for the level of braking torque. 0.
A055 DC braking
duration
– j 0 – 60 s The time during which DC braking is active. 0.0
A056 DC braking –
behaviour on
activation of
the digital
input (DB)
– j 00 Timed braking according to value of PNU A055 01
01 Continuous operation