Installation
10/05 AWB8230-1541GB
44
Inputs 1 to 5 all have the same function and mode of operation
except for terminal 5, which can also be configured as thermistor
input.
Inputs 1 to 5 are optically and electrically isolated from the built-
in control section (CPU). They are actuated with +24 V. You can
use the device’s internal control voltage from terminal P24 or an
external voltage source.
You can configure the actuation of inputs 1 to 5 for special control
circuits and national circuit types Table 11 shows the various
versions in dependence of the SR/SK microswitch. This switch is
located to the right of the control signal terminals and has two
switching contacts:
SR = source, positive switching logic (default settings)
SK = sink, negative switching logic
Figure 44: Control signal terminal strip (part 1)
1345L
RST
FF2
FF1
REV
FWD
+24 V
2 P24
SR SKSK SR
+
R
i
SR
SK
485
OPE
TM
PRG
Figure 45: Position of microswitches
SR
SK
485
OPE
TM
PRG
I
O
K12 K14 K11
AM
H
O
OI
L
L 5
4 3 2 1
P24
CM2
12 11
Warning!
Before you switch on the internal or external control
voltage, check the position of the SR/SK switch. An
incorrect setting can damage the control input.