Setpoint
Undertemp.
warning
Undertemperature warning
2 °C
D
Setpoint
Overtemp.
warning
Overtemperature warning [1]
2 °C
Setpoint
Overtemperature warning [2]
235 °C
455 °F
2 °C
D
Troubleshooting
6-7
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
Undertemperature and Overtemperature Warning
Alarm Triggered
Alarm Reset
Undertemperature Warning Triggered
The temperature has fallen below the setpoint by more than the differential
value (D) Undertemperature warning delta for longer than 5 seconds.
Automatic Reset
The temperature has increased to 2 °C (3.6 °F) below the setpoint.
Overtemperature Warning Triggered
[1] The temperature has exceeded the setpoint by more than the differential
value (D) Overtemperature warning delta for longer than 5 seconds.
or
[2] 235 °C (455 °F) was exceeded for longer than 5 seconds.
Automatic Reset
The temperature has fallen to 2 °C (3.6 °F) above the setpoint.