Operation
4-7
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
If the melter is to be operated via the interface Standard I/O, change the
motor enable from Control panel to Control panel AND standard I/O.
Refer to Control Panel − Overview − / M2.1
Standard I/O: Observe for edge-controlled signals (example)
If standby is switched on via the interface (rising edge), it can be switched
off with the seven-day clock or by the operator on the control panel
(Who-touched-me-last).
If standby is then to be switched on again via the interface, it must first be
switched off (falling edge) then on again via the interface.
Key-to-line − settings
Refer to Control Panel − Overview − / M1 to M3
Select temperature unit, °C (default) or °F
Select pressure unit: bar (default), psi or kPa
Refer to Control Panel − Overview − / V15
Set service interval.
The service tasks that are to be indicated as well as the intervals must
be stipulated. For recommended intervals refer to section Maintenance.
The intervals may need to be adapted to the operating conditions.
Refer to Control Panel − Overview − / V16
Additional parameters, depending on model of melter.
For example: Optimize level evaluation (Refer to Filling the Tank / Level)